When measuring battery capacity by conducting a discharge test, the TORKEL 860 provides excellent discharging capacity plus a broad voltage range and outstanding portability. The TORKEL 860 is used for systems ranging from 12 to 480 V, and discharging can proceed at up to 110 A. Discharging can take place at constant current, constant power, constant resistance or in accordance with a preselected load profile.
General
Mains voltage: 100 – 240 V AC, 50 / 60 Hz
Power consumption (max): 150 W
Protection: Thermal cut-outs, automatic overload protection
Current measurement
Display range: 0.0 – 2999 A
Basic inaccuracy: ±(0.5% of reading +0.2 A)
Resolution: 0.1 A
Internal current measurement
Range: 0 – 300 A
Input for clamp-on ammeter
Range: 0 – 1 V
mV/A-ratio Software: settable, 0.3 to 19.9 mV/A
Input impedance: >1 MΩ
Voltage measurement
Display range: 0.0 – 60 V
Basic inaccuracy: ±(0.5% of reading +0.1 V)
Resolution: 0.1 V
Display range: 0.0 – 500 V
Basic inaccuracy: ±(0.5% of reading +1 V)
Resolution: 0.1 V
Time measurement
Basic inaccuracy: ±0.1% of reading ±1 digit
Load
Max battery voltage: 480 V DC
Max current: 110 A
Max power: 15 kW
Load patterns: Constant current, constant power,constant resistance, current or power profile
Current setting: 0-110.0 A (2999.9 A) 1)
Power setting: 0-15.00 kW (299.99 kW) 1)
Resistance setting: 0.1-2999.8 Ω
Battery voltage range: 5 ranges, selected automatically at start of test
Stabilization: ±(0.5% of reading +0.5 A) (For internal current measurement)